HEAT LOSS REDUCTION IN HEAT EXCHANGE SYSTEMS AT THERMAL POWER PLANTS

Abstract: this article analyzes heat loss reduction methods in heat exchange systems at thermal power plants, focusing on efficiency improvement, fuel saving, and reduction of CO2 emissions. Calculation methods based on heat balance, logarithmic mean temperature difference, and fuel consumption models are provided.

Keywords: heat exchanger, heat loss, efficiency, optimization, thermal power plant, fuel economy.

Introduction: Currently, steam-gas plants with high efficiency are widely used in the energy system of our republic. At the same time, it is planned to put new steam-gas plants into operation. This is due to the fact that the efficiency of steam-gas plants is higher than that of steam turbine plants. Modern steam-gas plants are also distinguished by their compactness, ease of operation, full automation of control and the presence of a normal protection system.

In this regard, their study is considered relevant.In Azerbaijan, stations with steam and gas plants occupy a special place in energy production. The predominance of the operation of new thermal power plants of this type is the result of the technical improvement of these plants. This is mainly explained by the constant improvement of technical and economic indicators, the reduction of the amount of fuel per unit of energy and the low price. [1-4].Currently, the steam-gas plant "Shimal" ES, which is currently operated with high efficiency in the energy system of our republic, has a special significance. The first stage of the "Shimal" power plant was decommissioned in 1988, and the second stage in 1998 due to complete obsolescence.

Investment in the construction of the "Shimal-1" power plant was initiated by President Heydar Aliyev during his visit to Japan in 1998. The 400-megawatt "Shimal-1" power plant was commissioned in 2002. The foundation of the 400-megawatt "Shimal-2" power plant was laid in 2011, and construction work was completed in 2019. The combined capacity of the "Shimal-1" and "Shimal-2" power plants is 800 megawatts.

In order to manage the stations from a single center, a single control dispatch center has been established in the Central Building of the Administration. The total energy productivity of the "Shimal-1" and "Shimal-2" power plants is about 6.0 billion kilowatt-hours per year. Gas and steam turbines manufactured by the Japanese company "Mitsubishi" are operated at the station. The capacity of the gas turbine unit is 267 MW, and the capacity of the steam turbine unit is 138 MW.

A 560 MW electric generator and some auxiliary systems have been installed at the station. The purpose of installing two autotransformers is to connect distribution equipment with different voltages. The "Shimal" power plant meets more than 20 percent of the electricity demand of our republic. Currently, the "Shimal" power plant in operation mode operates with a useful work factor of 57.4 percent.

In order to supply the station with high-pressure gas, a gas pipeline (underground), a regulating junction with a gas regulator, a gas heating device and a compressor station are operated. The Caspian Sea water is used to cool the equipment at the station. In order to protect the environment, a reverse osmosis device, industrial waste and wastewater treatment devices are operated to prepare additional water.Since the "Shimal" ES is a modern and important station in the energy production system of Azerbaijan, the study of its operation is relevant. The capacity of the steam-gas unit installed at the "Shimal-1" ES is 400 MW.

The unit includes 1 gas turbine (M701 – F Mitsubishi model), 1 utility boiler, 1 steam turbine (TC2F – 35.4 type).The purpose of the work is to investigate the regime factors affecting the efficiency of the "Shimal-1" ES steam-gas plant. The efficiency of combined steam-gas plants depends on the separate efficiencies of the steam and gas cycles. The share of the effective power of the gas cycle in the efficiency of combined steam-gas plants can be increased by increasing the temperature of the gas (combustion products) at the turbine inlet or by increasing the pressure of the compressor.Fig. 1. Fig. 2.

Histogram of the dependence of P=F(∆tsag, (∆tsol,Gkon).Fig.1 and Fig.2 show histograms of the dependence of the vacuum in the condenser of the "Shimal-1" ES steam-gas plant on the condensing steam consumption, the heating of the cooling water and the temperature pressure in accordance with the right and left outlets of the condenser for the spring months. It can be seen from the histograms that at relatively constant values of the vacuum in the condenser in the operating mode, the values of the heating of the cooling water and the temperature pressure are relatively consistent with the nominal mode values. In order to obtain optimal efficiency, the considered parameters must be kept under control.Initial Data and AssumptionsFor one operational block of the Mingachevir Thermal Power Plant (TPP), the following typical data are considered:Total supplied thermal energy:Q1 = 1000GJUseful (converted to electrical) energy:Q2 = 920GJFuel type: natural gas with a lower calorific value:Hu = 34MJ/m3Thermal losses before optimization: approximately 8%Heat exchanger temperatures:Hot inlet T1 = 120°CHot outlet T2 = 80°CCooling water inlet t1 = 25°CCooling water outlet t2 = 35°CHeat Balance and Heat LossesThe general heat balance is expressed as: Q1 = Q2 + QlossHeat losses: Qloss = Q1 - Q2 = 80 GJPercentage of heat loss: δ = (80 / 1000) × 100% = 8%Thermal Efficiencyη = (Q2 / Q1) × 100% = (920 / 1000) × 100% = 92%Logarithmic Mean Temperature Difference (LMTD)ΔTlm = [(T1 − t2) − (T2 − t1)] / ln[(T1 − t2) / (T2 − t1)]Substituting values gives ΔTlm ≈ 68.9°C.Fuel ConsumptionTotal energy: 1000 GJ = 1,000,000 MJGas volume required: V = 1,000,000 / 34 ≈ 29,412 m³Optimization Scenario – Reduction of Heat LossesAfter optimization, losses decrease from 8% to 5%.New efficiency: ηnew = 95%Required thermal input: Q1_new ≈ 968.4 GJEnergy saved: 31.6 GJFuel saved: ≈ 929 m³CO2 Emission ReductionAssuming emission factor for natural gas: 1.9 kg CO2/m³CO2 reduction: ≈ 1.8 tons


Полная версия статьи PDF

Номер журнала «Вестник науки» № 12 (93) том 1


Ссылка для цитирования:

Neymatov S. HEAT LOSS REDUCTION IN HEAT EXCHANGE SYSTEMS AT THERMAL POWER PLANTS // Журнал «Вестник науки» от 7 декабря 2025 г. № 12 (93) том 1. С. 1881 - 1888. 2025 г. ISSN 2712-8849 // Электронный ресурс: https://www.вестник-науки.рф/article/27222 (дата обращения: 29.11.2026 г.)


Альтернативная ссылка латинскими символами: vestnik-nauki.com/article/27222



Нашли грубую ошибку (плагиат, фальсифицированные данные или иные нарушения научно-издательской этики) ?
- напишите письмо в редакцию журнала: zhurnal@vestnik-nauki.com


Вестник науки © 2025.    16+




* В выпусках журнала могут упоминаться организации (Meta, Facebook, Instagram) в отношении которых судом принято вступившее в законную силу решение о ликвидации или запрете деятельности по основаниям, предусмотренным Федеральным законом от 25 июля 2002 года № 114-ФЗ «О противодействии экстремистской деятельности» (далее - Федеральный закон «О противодействии экстремистской деятельности»), или об организации, включенной в опубликованный единый федеральный список организаций, в том числе иностранных и международных организаций, признанных в соответствии с законодательством Российской Федерации террористическими, без указания на то, что соответствующее общественное объединение или иная организация ликвидированы или их деятельность запрещена.