SELECTION OF PROTECTION AND AUTOMATION TYPES IN SUBSTATIONS: TECHNICAL ANALYSIS AND STRATEGIC IMPLEMENTATION

Abstract: this article examines the complex aspects of selecting and modernizing relay protection and automation systems in electrical substations, specifically focusing on those commissioned in the late XX century. As the energy sector evolves, the transition from electromechanical components to multifunctional digital microprocessor devices becomes essential for enhancing sensitivity and performance. The study analyzes the technical implementation of various protection types, including differential, distance, and zero-sequence current protection for 110 kV and 10 kV systems. Furthermore, it discusses the economic and technical advantages of digital systems, such as Logical Bus Protection, which allows for complex operations at the software level without additional hardware costs. The final result emphasizes that while traditional methods remain reliable, the integration of modern digital technologies is the most effective path for future energy infrastructure.

Keywords: energy systems, relay protection, substation automation, digital technologies, differential protection, distance protection, microprocessor systems.

Introduction. The reliability of any modern industrialized society is fundamentally based on its energy infrastructure. Within this framework, the effectiveness of relay protection and automation (RPA) devices is paramount for maintaining system stability. According to the analysis of the element base used, RPA equipment can be categorized into three distinct generations: Electromechanical devices: These are based on traditional physical components and moving parts, Microelectronic devices: These utilize analog semiconductors and represented the first step toward modernization, Digital (microprocessor-based) devices: These represent the current state-of-the-art, offering multifunctional capabilities and software-driven logic [1-3].

The shift toward digital protection is not merely a change in hardware but a fundamental improvement in how fault algorithms are processed, removing previous limitations on complexity and significantly increasing the speed of response. Setting the main issue. The primary challenge in the modernization of power systems lies in the fundamental shift between different generations of relay protection and automation (RPA) units. While the core objectives of protection—reliability, selectivity, speed, and sensitivity—have remained constant since the inception of power engineering, the methods by which these objectives are achieved have undergone a radical transformation.

In older installations, such as those designed in the late 1960 s, the protection infrastructure is predominantly based on electromechanical components. For instance, in the application of transformer differential protection, classic devices like the RNT-565 relay must physically compensate for the inequalities in current transformer (CT) ratios and the phase shifts caused by different winding connections. This is achieved through the use of intermediate saturating transformers, which require precise manual adjustments and physical calibration to prevent false operations during magnetizing inrush currents (BCT). This physical «balancing» creates a rigid system that is difficult to reconfigure and prone to mechanical wear over decades of service.

The main issue emerges when we transition to microprocessor-based (digital) systems. In a digital environment, the physical constraints of the relay are replaced by mathematical models [4]. The compensation for current magnitude and phase angle is no longer a physical process involving magnetic flux in a transformer core, but a software-based calculation involving vector manipulation. This allows for much higher precision, however, it introduces a new layer of complexity: the requirement for robust algorithms that can distinguish between a genuine internal fault and transient phenomena like CT saturation or inrush currents [5-9].

Furthermore, the introduction of digital systems allows for the implementation of features that were previously deemed technically or economically impractical. A key example is the use of the second harmonic component for blocking differential protection during transformer energization. Digital terminals, by contrast, utilize Fast Fourier Transform (FFT) algorithms to extract harmonic data instantaneously, providing a level of security and sensitivity that older generations simply cannot match. The modernization issue extends to the coordination of different protection zones.

In a 110/10 kV substation, the protection must ensure absolute selectivity for the transformer while maintaining relative selectivity for the outgoing 10 kV feeders and 110 kV lines[10]. Modernization Strategies and Technical Implementation of Digital RPA. Systems in 110/10 kV Substations: The transition from electromechanical to digital (microprocessor-based). relay protection and automation (RPA) systems in substations commissioned in the late 1960s requires a structured modernization strategy. This strategy must address not only hardware replacement but also the integration of advanced communication protocols, improved fault detection algorithms, and enhanced system reliability.

One of the key technical advantages of digital systems lies in their ability to implement complex protection logics through software rather than physical wiring. For instance, Logical Bus Protection, which was mentioned earlier, can be realized using low-impedance differential principles in modern numerical relays. In traditional electromechanical setups, busbar protection often relied on high-impedance differential schemes requiring dedicated CT circuits and extensive auxiliary relays. In contrast, digital relays support dynamic bus replica functionality, where current inputs are logically assigned to protection zones based on disconnector and circuit breaker status signals.

This eliminates the need for physical current switching and reduces the risk of incorrect zone configuration during busbar reconfiguration [11-15]. Modern digital busbar protection schemes process multiple current inputs (often 10–20 or more) in a centralized or distributed architecture. They incorporate breaker failure protection, sequence of events recording, and oscillography as built-in functions, significantly reducing panel space and wiring complexity compared to electromechanical equivalents. Studies show that a typical electromechanical bus protection scheme using 8–10 relays can be replaced by one or two multifunctional microprocessor relays, achieving faster operating times (typically under 1 cycle for internal faults) while maintaining high security against external faults and CT saturation.

In the context of transformer differential protection, the shift from devices like RNT-565 to numerical relays brings substantial improvements. Electromechanical relays use intermediate saturating transformers for ratio and phase compensation, which are sensitive to manufacturing tolerances and aging. Digital relays perform these compensations mathematically using vector transformations and phasor estimation techniques, such as the Discrete Fourier Transform (DFT) or Full Cycle Fourier algorithms. This allows precise compensation for CT ratio mismatches, vector group shifts (e.g., Yd11), and zero-sequence current filtering without additional hardware.

A critical enhancement in digital transformer protection is the use of harmonic restraint and blocking. The second harmonic component is extracted via Fast Fourier Transform (FFT) to block operation during magnetizing inrush currents, while the fifth harmonic can block during overexcitation. Advanced algorithms also incorporate DC component detection and even-harmonic restraint to improve security during external faults with severe CT saturation, without compromising sensitivity for low-level internal turn-to-turn faults. Negative-sequence differential elements further increase sensitivity to minor winding faults that traditional percentage differential relays might miss.

For 110 kV transmission lines, distance protection remains a primary method due to its selectivity and ability to provide backup protection. Electromechanical distance relays (e.g., impedance or mho characteristics) suffer from limitations in setting flexibility and transient response. Digital distance relays implement polygonal or quadrilateral characteristics with multiple zones (Zone 1, 2, 3, and sometimes Zone 4 for backup). They support power swing blocking, load encroachment prevention, and tele-protection schemes via high-speed communication channels [16-19].

Digital implementation allows adaptive settings based on system conditions and integration with line differential protection for enhanced performance on parallel lines or series-compensated circuits. Operating times are significantly reduced (sub-cycle for close-in faults), and the relays provide detailed fault location information, aiding rapid restoration. At the 10 kV level, zero-sequence current protection (earth fault protection) plays a vital role, especially in networks with isolated or resonant-earthed neutrals. Traditional schemes use core-balance current transformers (zero-sequence CTs) connected to sensitive overcurrent relays.

In digital systems, this function is integrated into feeder protection IEDs with adjustable settings for residual current (3I0) and zero-sequence voltage (U0). The integration of IEC 61850 standard represents a paradigm shift in substation automation. This international standard enables interoperability between devices from different manufacturers through standardized data models (Logical Nodes), GOOSE messaging for high-speed peer-to-peer communication, and Sampled Values (SV) for process bus applications. In a 110/10 kV substation, IEC 61850 eliminates much of the conventional copper wiring between relays, merging units, and bay controllers, reducing installation costs by up to 50–70% and minimizing commissioning time.

It also facilitates centralized protection schemes and easier future expansions. The result. The comprehensive analysis conducted in this study demonstrates that the modernization of relay protection and automation (RPA) systems in 110/10 kV substations is a strategic necessity for the stability of the modern power grid. Unlike traditional relays such as the RNT-565, which rely on physical components and manual calibration, digital terminals utilize advanced mathematical algorithms and Fast Fourier Transforms (FFT) to filter signals with high accuracy.

This ensures that faults are localized and cleared within milliseconds, preserving the dynamic stability of the 110 kV network.


Полная версия статьи PDF

Номер журнала «Вестник науки» № 4 (97) том 1


Ссылка для цитирования:

Shikhaliyeva S.Y., Ismayilov N.Z. SELECTION OF PROTECTION AND AUTOMATION TYPES IN SUBSTATIONS: TECHNICAL ANALYSIS AND STRATEGIC IMPLEMENTATION // Журнал «Вестник науки» от 5 апреля 2026 г. № 4 (97) том 1. С. 1038 - 1044. 2026 г. ISSN 2712-8849 // Электронный ресурс: https://www.вестник-науки.рф/article/29627 (дата обращения: 29.11.2026 г.)


Альтернативная ссылка латинскими символами: vestnik-nauki.com/article/29627



Нашли грубую ошибку (плагиат, фальсифицированные данные или иные нарушения научно-издательской этики) ?
- напишите письмо в редакцию журнала: zhurnal@vestnik-nauki.com


Вестник науки © 2026.    16+




* В выпусках журнала могут упоминаться организации (Meta, Facebook, Instagram) в отношении которых судом принято вступившее в законную силу решение о ликвидации или запрете деятельности по основаниям, предусмотренным Федеральным законом от 25 июля 2002 года № 114-ФЗ «О противодействии экстремистской деятельности» (далее - Федеральный закон «О противодействии экстремистской деятельности»), или об организации, включенной в опубликованный единый федеральный список организаций, в том числе иностранных и международных организаций, признанных в соответствии с законодательством Российской Федерации террористическими, без указания на то, что соответствующее общественное объединение или иная организация ликвидированы или их деятельность запрещена.