COMPARATIVE ASSESSMENT OF VACUUM AND SF₆ CIRCUIT BREAKERS BASED ON OPERATIONAL RELIABILITY AND LIFE-CYCLE COST
Abstract: this study presents a comparative analysis of vacuum and SF₆ circuit breakers used in medium- and high-voltage AC power networks. The evaluation is based on a comprehensive approach that integrates regulatory compliance, operational reliability, and life-cycle cost indicators. Special attention is given to the influence of switching frequency, fault current interruption conditions, and maintenance requirements on equipment performance. The proposed methodology includes the analysis of switching operation logs, failure statistics, and maintenance records to determine key reliability indicators such as failure rate, restoration time, and the share of unplanned maintenance activities. The life-cycle cost structure incorporates capital investment, scheduled maintenance, unscheduled repairs, and costs associated with feeder unavailability. The results show that the predictability of maintenance and failure risk management are more critical than nominal service life under conditions requiring high feeder availability. It is also demonstrated that the condition of the contact system in SF₆ circuit breakers significantly affects both reliability and maintenance costs under severe operating conditions.
Keywords: vacuum circuit breaker, SF6 circuit breaker, operational reliability, life cycle cost, switching operations, failure rate.
Switching devices in alternating current (AC) power networks play a key role in ensuring the reliable interruption of short-circuit currents and significantly influence the operational stability of network feeders during switching processes. The subject of this study is vacuum and SF₆ circuit breakers, which are widely used in switchgear installations of electrical power systems operating under conditions characterized by long steady-state modes combined with frequent switching operations. In this study, the comparison of these technologies is not limited to a simple evaluation of individual catalog parameters. Instead, it is considered as a comprehensive assessment based on operational reliability and life-cycle cost indicators.
The operational duties of a circuit breaker are defined as a sequence of switching operations, including the interruption of faulted network sections, in accordance with the testing and operational conditions specified in IEC 62271-100. The engineering relevance of the problem lies in the fact that a circuit breaker failure leads to an expansion of the disconnection zone and an increase in the time required to restore the network configuration. This results in a deterioration of power supply reliability for the corresponding feeder. At the same time, the total life-cycle cost of switching equipment is determined not only by the initial capital investment but also by maintenance requirements, repair labor intensity, and equipment downtime during maintenance and repair [1-3].A significant limitation in selecting circuit breaker technology is that decisions are often based solely on rated voltage and current values, while insufficient attention is given to switching frequency and the characteristics of interrupted currents under real operating conditions.
These effects manifest themselves in an increasing share of unplanned maintenance activities, rising operational costs, and a decline in reliability indicators of electrical power networks. In practical operation, this may appear either as increased sensitivity of the equipment to the condition of the mechanical operating mechanism or as the need for more complex procedures for monitoring the working medium and ensuring system tightness, ultimately affecting feeder availability [20]. The dependence of failure rate on switching intensity is illustrated in Figure 1, which shows that the failure rate increases with the number of switching operations. At the same time, different technologies demonstrate different rates of degradation under repeated switching conditions.
The scope of this study is limited to medium- and high-voltage AC power networks, where circuit breakers perform standard switching functions and operate within established maintenance regulations. Issues related to insulation coordination and relay protection are not considered separately, as they are assumed to be addressed during the design stage of the power system. Fig. 1. Failure rate as a function of switching operations.
The fundamental assumption of this work is that the operational duties of a circuit breaker can be characterized using switching operation logs, defect reports, and recorded maintenance intervals obtained during equipment operation [4-8]. In engineering practice, the selection of switching equipment is typically based on a combination of regulatory requirements, operational statistics, and life-cycle cost evaluation. A comparison of these approaches shows that the regulatory level ensures compliance but does not reflect the distribution of failures among key components. The operational level provides a more realistic assessment but requires accurate data collection.
The economic level is highly sensitive to input data completeness, while providing a direct link between reliability and cost indicators [9-13]. The dynamics of maintenance costs over the equipment lifetime are presented in Figure 2. Fig. 2. Maintenance cost over time.
It can be observed that maintenance costs increase over time and are influenced. by both the frequency of switching operations and the complexity of servicing procedures [19]. For the stated objective, a combined approach is the most appropriate. In this approach, compliance with regulatory requirements is considered a necessary condition, while the comparison of technologies is performed based on failure mechanisms and maintenance structure. This reduces the risk of selecting equipment that formally meets specifications but is not suitable under real operating conditions.
The proposed methodology includes the characterization of feeder operating conditions, identification of key reliability indicators (failure rate, mean restoration time, and share of unplanned maintenance), and evaluation of life-cycle costs, including procurement, scheduled maintenance, unscheduled repairs, and costs associated with feeder unavailability. The structure of maintenance activities is illustrated in Figure 3, where the proportion of planned and unplanned maintenance is shown. A higher share of unplanned maintenance is associated with increased operational risks and reduced predictability of equipment performance [14-18]. The validity of the results is verified through consistency with physically justified degradation mechanisms and analysis of boundary operating conditions.
If calculated costs increase without a clear link to operational factors, this indicates insufficient input data. Fig. 3. Structure of maintenance activities. Conclusion.
The first conclusion is that under conditions requiring high feeder availability, the decisive factor is not the nominal service life but the predictability of maintenance and effective failure risk management. The availability of condition monitoring and maintainability of equipment design become critical factors. The second conclusion is that for SF₆ circuit breakers, the condition of the contact system after fault current interruption significantly affects both reliability and life-cycle costs. Contact wear and erosion determine maintenance frequency and must be taken into account when selecting equipment for severe operating conditions.
The practical recommendation is that the comparison of circuit breaker technologies should not rely solely on calendar-based maintenance schedules. Instead, it should be based on models that consider actual switching intensity and operating conditions.
Полная версия статьи PDF
Номер журнала «Вестник науки» № 4 (97) том 2
Ссылка для цитирования:
COMPARATIVE ASSESSMENT OF VACUUM AND SF₆ CIRCUIT BREAKERS BASED ON OPERATIONAL RELIABILITY AND LIFE-CYCLE COST // Журнал «Вестник науки» от 12 апреля 2026 г. № 4 (97) том 2. С. 1033 - 1039. 2026 г. ISSN 2712-8849 // Электронный ресурс: https://www.вестник-науки.рф/article/29754 (дата обращения: 29.11.2026 г.)
Альтернативная ссылка латинскими символами: vestnik-nauki.com/article/29754
Нашли грубую ошибку (плагиат, фальсифицированные данные или иные нарушения научно-издательской этики) ?
- напишите письмо в редакцию журнала: zhurnal@vestnik-nauki.com