STUDY OF POWER REDISTRIBUTION DURING SEPARATE OPENING OF DIFFERENT LINES IN COMPLEX CLOSED NETWORKS
Abstract: in complex closed power networks, the planned or accidental opening of individual lines causes significant changes in the systems regime parameters and shapes the process of power redistribution. This article studies from a theoretical and analytical perspective how active and reactive power flows, voltage levels, and current distribution are transformed during the decommissioning of one or more transmission lines in power systems with a closed topology. The main goal of the study is to determine the mechanism of the impact of line openings on the stability of the system, load level, and losses, as well as to present a scientifically justified approach for the selection of critical elements. The paper explains the regularities of power distribution changes by applying equivalent circuits, load flow equations, and sensitivity analyses for closed networks. The results show that the structural features of the network and the generation-consumption balance are the main factors determining the nature of the reaction to line openings. The conducted analyses are of great practical importance in terms of optimizing operational management decisions, preventing accidents, and increasing reliability in complex power systems.
Keywords: node, conductivity, voltage, reactance, power, power flow, post-crash state, cascading failure.
Modern electric power systems have acquired complex structural features as a result of the mutual integration of diverse production sources, transmission lines of different voltage levels, and distribution networks covering a large geographical area. In particular, networks with a closed (ring) topology are considered superior in terms of providing high reliability and alternative energy transmission routes. However, the opening of individual lines in such networks due to planned maintenance, reconstruction, or accidents creates sudden changes in the structure of power flows and, as a result, leads to a redistribution of load across the system. Improper assessment of this process can lead to local load increases, voltage deviations, and even cascading failures.
At the present stage, the analysis of power systems is mainly carried out using load flow models, static and dynamic stability criteria, as well as sensitivity factors. However, the issue of accurately determining in advance the degree of impact of opening specific lines on the system in complex closed networks still remains an urgent scientific problem. Although some approaches assume that structural redundancy of the network reduces risks, according to an alternative view, numerous parallel connections can in certain cases lead to uneven distribution of power and unexpected loading of critical elements. In this regard, the purpose of the presented work is to systematically analyze the mechanism of redistribution of active and reactive powers during the opening of individual lines in complex closed networks, to assess the impact of these changes on the operational reliability of the network and to form an analytical basis for determining critical modes.
The research is of great importance in terms of strengthening the scientific foundations of decision-making in the operational management and planning process of energy systems. 1. Fundamental Reasons for Power Redistribution in Complex Closed Networks. In closed-configuration electrical networks, the individual opening of any line (whether due to the effect of the emergency protection system or as a result of operational switching) leads to radical changes in the physical and mathematical model of the system. The explanation of this phenomenon at the academic level is based on the following four fundamental reasons: 1.1.
Change in Network Topology and Equivalent Conductivity: In closed networks, power flows are distributed depending on the electrical distance between nodes and the resistance of the lines. When a line leaves the circuit, the incidence matrix of the network and, accordingly, the nodal permeability matrix are modified. Mathematically, the opening of a line means an increase in the total equivalent resistance of the network. In this case, according to Kirchhoffs first and second laws, the electric current immediately diverts to alternative paths (parallel branches) with less resistance. 1.2.
The Effect of Electrical Distance Length and Impedance. In complex networks, the «electrical distance» between generators and loads is measured not only by geographical distance, but also by the impedance of the lines. When a main line fails, power is forced to be transported through lines with longer or higher reactive resistance. This leads to a nonlinear increase in the reactive power losses of the lines, resulting in a deterioration of the voltage profile in the system. 1.3.
Phase Angle Shift of Node Voltages. In closed circuits, the active power flow (P) is proportional to the difference in voltage angles (δ) between two nodes: ???=??∙?????(sin??−??). ???- (Active power flow): represents the amount of active power transferred from node to node (or vice versa). The unit of measurement is usually megawatts. ?? və ??-(Nodal voltages): These are the effective values of the voltages at nodes ? and ?, respectively. Although the voltage modulus is kept constant in closed networks, these values change when the line is opened. ???-(Line reactance): It is the inductive resistance of the line connecting nodes ? and ?.
In complex networks, this quantity is the main obstacle that determines which way power will «flow». The smaller the resistance, the more load the line tends to carry. ?? and ??- (Load Angle Difference): The phase difference between two nodes. This angle difference is the main force that causes power to be «pushed» from one point to another. When a line is opened, the phase angles of the nodes are automatically readjusted to ensure power flow on other lines that accept the load.
This dynamic shift reduces the static stability margin of the system and in some cases creates the risk of generator synchronous operation. 1.4. Disruption of the Energy Balance of Magnetic Fields. The opening of lines directly affects the reactive power balance of the network. Long lines exhibit both inductance and capacitance properties (reactive power generated by the line) in normal mode.
The opening of a line results in an increase in inductive losses due to the loss of this generation source and, at the same time, a greater load on the remaining lines. This imbalance is the main factor that creates the basis for the chaotic distribution of power flows in the network and voltage collapse. 2. Research Methodology through LODF- Line Outage Distribution Factor. In the analysis of the regimes of complex closed networks, the LODF coefficient is the most effective mathematical tool for quickly assessing the post-accident situation.
This coefficient quantifies how the opening of one line affects the load level of other lines. 2.1. Mathematical Definition of LODF. If line l (the emergency line) in the network is opened, the change in power passing through any other line m (the monitored line) is determined by the following dependence: ?????,?=∆????0. ?????,?- ? as a result of the opening of the line ? is the share coefficient falling on the line. ∆?? -? is the amount of increase in the active power flow on the line. ??0- ? is the active power flowing through the line before it is opened (in normal mode). 2.2. Finding a New Power Flow in the Post-Crash Regime. ? any remaining in the network after the line is opened ?
The new load level of the line can be calculated with this formula: ??????−????ℎ=??0+ (?????,?×??0). ??????−????ℎ- After the line is opened ? the new amount of power carried by the line. ??0- In the initial (normal) state of the network ? power passing through the line. ?????,?×??0 - «Slips» from the opening line and the part of the power added to the line ?. 1. Sensitivity Analysis: If the calculations show that ?????,? If the coefficient is close to 1 or greater than 1, this, ? it indicates that the risk of overloading the ? line is very high and that there is a possibility of a cascade failure in the system. 2.This coefficient is only due to the resistance of the lines. (???) and depends on the network connection scheme.
That is, regardless of the voltage level, the network structure predetermines the power distribution «route». 3. Implementation of the «N-1» criterion and strategies for preventing cascading accidents. The most important safety standard in the operation of complex closed networks is the «N-1» reliability criterion. This criterion requires that if any key element in the system (power transmission line, transformer or generator) fails, the remaining infrastructure must ensure the power supply of consumers without interruption and without overloading other elements. 3.1.
N-1 analysis and identification of critical points. In the power redistribution study, each line opening scenario is simulated separately. At this time, the «criticality index» of the network is calculated. If a line opening (for example, line ?1) on other lines (for example, ?2,?3 ) current limit (İ???) If it causes the line to rise, that line is considered a «weak point.» Mathematically, this situation is expressed as follows: ?????−????ℎ≤İ?ℎ?????−???.
Here ?????−????ℎ is the new current value in the remaining branches after the line is opened. If this inequality is violated, there is a risk of a cascade accident in the system. 3.2. Mechanism of cascade accidents and chain reaction. Cascade failure is the process of redistributing power as a result of the opening of one element, causing other elements to exceed their load limits and be sequentially removed from the circuit by protection systems.
This process occurs in a very short time and can lead to a complete collapse (Blackout) of large energy systems. To prevent this, research work monitoring ???? rartios is mandatory. 3.3. Anti-accident automation and mode control. The following operational and technical measures are being implemented to neutralize the negative effects of the redistribution of forces: Automatic Load Shedding (ALS): If the stability of the system is threatened after the line is opened, special automation restores the generator and line balance by disconnecting irresponsible consumers from the network.
Reactive Power Compensation: Modern devices such as STATCOM or SVC are used to compensate for the voltage drop caused by line opening. Topological Changes: In some cases, power flows are redirected to more «safe» routes by connecting other backup branches or changing the network configuration through dispatcher control. RESULT. Studies have shown that in complex closed networks, individual line openings directly affect both the static and dynamic stability of the system.
The process of power redistribution is determined not only by proximity in terms of distance, but also by the ratio of the reactive resistances of the lines and the phase angle shifts of the nodes. Analyses using LODF coefficients allow for the early identification of critical load points in the network. Consequently, the provision of the «N-1» criterion and the introduction of modern anti-accident automation systems are the main factors ensuring the stable operation of complex networks in post-accident modes.
Полная версия статьи PDF
Номер журнала «Вестник науки» № 5 (98) том 2
Ссылка для цитирования:
STUDY OF POWER REDISTRIBUTION DURING SEPARATE OPENING OF DIFFERENT LINES IN COMPLEX CLOSED NETWORKS // Журнал «Вестник науки» от 10 мая 2026 г. № 5 (98) том 2. С. 1530 - 1536. 2026 г. ISSN 2712-8849 // Электронный ресурс: https://www.вестник-науки.рф/article/30339 (дата обращения: 29.11.2026 г.)
Альтернативная ссылка латинскими символами: vestnik-nauki.com/article/30339
Нашли грубую ошибку (плагиат, фальсифицированные данные или иные нарушения научно-издательской этики) ?
- напишите письмо в редакцию журнала: zhurnal@vestnik-nauki.com