EXPERIMENTAL INVESTIGATION OF THE BEARING CAPACITY OF DRIVEN PILES IN COLLAPSIBLE SOILS

Abstract: this paper presents the results of an experimental investigation into the bearing capacity of driven piles in collapsible soils at the Pulp Mixing Section of the Ertis Hydrometallurgical Combine in Pavlodar, Kazakhstan. The relevance of this study stems from the widespread occurrence of collapsible soils in Kazakhstan and the need to improve the reliability of foundations for industrial buildings and structures under such ground conditions. This study aims to determine the effect of the collapsible properties of the upper soil layer on the bearing capacity of C110.30-9 driven piles and to formulate practical recommendations for pile testing and design. Field static load tests under compressive and tensile loading were conducted in accordance with GOST 5686-2020. The testing procedure included preliminary wetting of the collapsible sandy loam layer to a depth of 2.80 m. The tested piles were 11.0 m long and had a cross-sectional dimension of 300 × 300 mm. The maximum applied compressive load was 483 kN, while the maximum tensile load was 332 kN. The experimental results provide a basis for evaluating the bearing capacity of piles under pre-wetted ground conditions. The findings may be used in the design of pile foundations for industrial facilities located in areas with collapsible soils.

Keywords: driven piles, bearing capacity, collapsible soils, static load testing, soil pre-wetting, pile foundations.

https://doi.org/10.68367/33712

УДК 624.154

Yelshibekov D.M.

first-year Master's student

Educational Program in Construction

Karaganda Technical University named after Abylkas Saginov

(Karaganda, Kazakhstan)

 

Baideldinova G.M.

PhD, Assistant Professor

Faculty of Mechanical Engineering

Department of Foreign Languages

Karaganda Technical University named after Abylkas Saginov

(Karaganda, Kazakhstan)

 

EXPERIMENTAL INVESTIGATION OF THE BEARING
CAPACITY OF DRIVEN PILES IN COLLAPSIBLE SOILS

 

Abstract: this paper presents the results of an experimental investigation into the bearing capacity of driven piles in collapsible soils at the Pulp Mixing Section of the Ertis Hydrometallurgical Combine in Pavlodar, Kazakhstan. The relevance of this study stems from the widespread occurrence of collapsible soils in Kazakhstan and the need to improve the reliability of foundations for industrial buildings and structures under such ground conditions. This study aims to determine the effect of the collapsible properties of the upper soil layer on the bearing capacity of C110.30-9 driven piles and to formulate practical recommendations for pile testing and design. Field static load tests under compressive and tensile loading were conducted in accordance with GOST 5686-2020. The testing procedure included preliminary wetting of the collapsible sandy loam layer to a depth of 2.80 m. The tested piles were 11.0 m long and had a cross-sectional dimension of 300 × 300 mm. The maximum applied compressive load was 483 kN, while the maximum tensile load was 332 kN. The experimental results provide a basis for evaluating the bearing capacity of piles under pre-wetted ground conditions. The findings may be used in the design of pile foundations for industrial facilities located in areas with collapsible soils.

 

Keywords: driven piles, bearing capacity, collapsible soils, static load testing, soil pre-wetting, pile foundations.

 

Static load tests on driven reinforced concrete piles were conducted at the construction site of the Ertis Hydrometallurgical Combine, specifically at the Pulp Mixing Section of the Hydrometallurgical Workshop, Processing Complex (USPK), in Pavlodar, Republic of Kazakhstan. Field tests of driven piles under static compressive and tensile loading were performed by specialists from KGS-Astana LLP in accordance with test program KGS-PR-2026-045-DP-SLT [6].

In accordance with the technical specification, trial driven piles of type C110.30-9, measuring 300 × 300 mm in cross-section and 11.0 m in length, were subjected to static load testing. The static load testing (SLT) method was employed to evaluate the bearing capacity of the piles. It is considered one of the most reliable field methods for assessing pile performance under applied loads. The tests were carried out in accordance with the requirements of GOST 5686-2020 «Soils. Field test methods by piles» [1] and SP RK 5.01-103-2013 «Pile foundations» [2].

A characteristic feature of the soil conditions of the site is the presence of collapsible sandy loam (EGE-1) of hard consistency with a thickness of 1.8–2.6 m in the upper part of the section. The absolute elevation of the natural ground surface is 121.40–121.98 m. Below the collapsible layer lie dense water-saturated dusty sand (EGE-2, thickness 2.2–4.5 m), soft-plastic heavy sandy loam (EGE-3), medium and fine sands, and hard clays. The groundwater level is recorded at a depth of 3.5–3.7 m (absolute elevation 118.38–117.55 m) [5].

Due to the collapsibility of the upper soil layer, in accordance with the requirements of clause 4.6 of GOST 5686-2020 [1], the soil was pre-wetted to a depth of 2.80 m to an absolute elevation of 116.95 m before the start of testing. Wetting began before the tests and continued until their completion [6]. This measure is mandatory for obtaining reliable values of bearing capacity under conditions that correspond to the possible flooding of the base during operation of the industrial facility.

The absolute elevation of the pit bottom for testing was 119.800 m, and the design elevation of the pile tip was 111.90 m. Pile driving was carried out after a «rest» period of at least 6 days. The number of tested piles was as follows: 2 piles under static compressive loads (piles No. 12 and 42) and 3 piles under pull-out loads (piles No. 13, 19 and 39).

 

Table 1. Summary of static load testing parameters for C110.30-9 driven piles.

Parameter Compressive Pull-out Unit Notes
Number of piles 2 (No. 12, 42) 3 (No.
13, 19, 39)
pcs Total 5 tests
Pile length / section 11.0 / 300×300 11.0 / 300×300 m / mm Driven piles
Design load 294.3 147.15 kN 30 t / 15 t
Maximum test load 483 332 kN According
to program
Stabilization criterion ≤ 0.10 mm / 1 h ≤ 0.10 mm / 2 h mm GOST 5686-2020
Max allowed settlement ≤ 20 ≤ 10 mm Program limit
Pre-wetting depth 2.80 2.80 m Collapsible layer

 

The load on the pile was applied using hydraulic jacks (Enerpred DG200P150 for compressive tests and DG100P200 for pull-out tests) with Enerpac hand pumps. Load and displacement measurements were performed by the SLT2 monitoring system with Load Cell dynamometers and electronic displacement transducers.

The reaction system consisted of metal frames and calibrated reinforced concrete blocks with a total weight of up to 133 tons. All structures of the reaction system were designed for a load exceeding the maximum test load by at least 20% [6, 7].

During compressive tests, the load was applied in ten stages up to a maximum value of 483 kN (design load 294.3 kN). Each stage was maintained until conditional stabilization of deformation was reached (displacement difference of no more than 0.10 mm during the last hour of observation).

During pull-out tests, the maximum load was 332 kN (design load 147.15 kN), and the stabilization criterion was no more than 0.10 mm during the last 2 hours of observation. Unloading was performed in stages equal to double the loading increments.

 

Figure 1. Graph of the dependence of pile settlement
S on load P and the change in pile settlement S over
time t (by load steps) for driven pile C110.30-9 No.912.

 

Figure 2. Comparison of design loads and maximum applied test loads
for compressive and pull-out static tests of driven piles C110.30-9.

 

Figure 3. Sequence of load steps during static compressive tests of piles
C110.30-9 (according to the test program KGS-PR-2026-045-DP-SLT).

 

The test results were processed in accordance with Clause 8.7 of GOST 5686-2020 [1]. The bearing capacity of the piles was determined by applying the relevant working condition and soil reliability factors in accordance with SP RK 5.01-103-2013 [2].

An analysis of the load–settlement curves (Fig. 1) and a comparison of the design loads with the maximum applied test loads (Fig. 2) indicate that the tested piles sustained compressive loads substantially exceeding the design load of 294.3 kN. The maximum applied compressive load of 483 kN was approximately 1.64 times the design load, while the measured settlements remained within the specified allowable limits. The stepwise loading diagram (Fig. 3) demonstrates a stable increase in load with controlled stabilization at each stage, which is a necessary condition for obtaining reliable data on the bearing capacity of piles in collapsible soils after wetting.

For pull-out tests the maximum applied load of 332 kN is more than twice the design value of 147.15 kN. This indicates a substantial safety margin of the piles against uplift forces, which is especially important for industrial structures that may experience additional vertical tensile loads during operation.

The experimental results confirm the importance of accounting for soil collapsibility when determining the design bearing capacity of driven piles. Pre-wetting the soil provides a more representative assessment of pile performance under ground conditions that may develop during the operation of foundations in collapsible soils [1, 3].

Based on the results of the tests, the following practical recommendations can be formulated:

1. For pile foundations constructed under Type I collapsible soil conditions, static load testing with preliminary soil wetting should be considered to assess the bearing capacity under anticipated wetting conditions. The wetting depth should correspond to the full thickness of the collapsible layer or to the depth specified in the approved testing program [1, 6].

2. The design bearing capacity of C110.30-9 driven piles under compressive loading may be revised based on the results of static load tests, provided that the relevant requirements of SP RK 5.01-103-2013 [2] are satisfied and the appropriate safety and reliability factors are applied.

3. For structures sensitive to differential settlement, monitoring of pile displacements during the initial years of operation is recommended, particularly during periods of seasonal groundwater-level fluctuations.

4. The experimental data can be used to validate and refine numerical models of pile–soil interaction under pre-wetted collapsible soil conditions.

The findings of this study may be applied in the design of pile foundations for industrial facilities constructed on collapsible soils in Kazakhstan, particularly at the Ertis Hydrometallurgical Combine and other industrial sites with comparable geotechnical conditions in the Pavlodar region.

 

REFERENCES:

 

1. GOST 5686-2020. Soils. Field test methods by piles. Moscow: Standartinform, 2020. 42 p.

2. SP RK 5.01-103-2013. Pile foundations. Astana: Committee for Construction, Housing and Communal Services, 2013. 78 p.

3. SP RK 5.01-102-2013. Bases of buildings and structures. Astana: Committee for Construction, Housing and Communal Services, 2013. 94 p.

4. GOST 30672-2012. Soils. Field tests. General provisions. Moscow: Standartinform, 2013. 12 p.

5. Technical report on engineering and geological surveys at the Ertis Hydrometallurgical Combine site. Arch. No. 01-25. Astana: KGS-Astana LLP, 2025. 186 p.

6. KGS-PR-2026-045-DP-SLT. Program of static load tests of driven piles C110.30-9 by compressive, pull-out and horizontal loads. Pavlodar: KGS-Astana LLP, 2026. 56 p.

7. SP RK 5.01-101-2013. Earthworks, bases and foundations. Astana, 2013.


Полная версия статьи PDF

Номер журнала «Вестник науки» № 11 (104) том 1


Ссылка для цитирования:

Yelshibekov D.M., Baideldinova G.M. EXPERIMENTAL INVESTIGATION OF THE BEARING CAPACITY OF DRIVEN PILES IN COLLAPSIBLE SOILS // Журнал «Вестник науки» от 1 ноября 2026 г. № 11 (104) том 1. С. 873 - 879. 2026 г. ISSN 2712-8849 // Электронный ресурс: https://www.вестник-науки.рф/article/33712 (дата обращения: 10.11.2026 г.)


Альтернативная ссылка латинскими символами: vestnik-nauki.com/article/33712



Нашли грубую ошибку (плагиат, фальсифицированные данные или иные нарушения научно-издательской этики) ?
- напишите письмо в редакцию журнала: zhurnal@vestnik-nauki.com


Вестник науки © 2026.    16+




* В выпусках журнала могут упоминаться организации (Meta, Facebook, Instagram) в отношении которых судом принято вступившее в законную силу решение о ликвидации или запрете деятельности по основаниям, предусмотренным Федеральным законом от 25 июля 2002 года № 114-ФЗ «О противодействии экстремистской деятельности» (далее - Федеральный закон «О противодействии экстремистской деятельности»), или об организации, включенной в опубликованный единый федеральный список организаций, в том числе иностранных и международных организаций, признанных в соответствии с законодательством Российской Федерации террористическими, без указания на то, что соответствующее общественное объединение или иная организация ликвидированы или их деятельность запрещена.